Among those core online al/pvc sheathed cable suppliers, Taiyuan Shangshang Cable Sales Co.,Ltd is a voltage supply al/pvc sheathed cable provider and manufacturer, welcome to buy our best al/pvc sheathed cable on the Internet or check the price with our factory and company.

Al/PVC sheathed cable
Specifications

1 Conductor:Copper or Aluminium
2 Insulation:PVC
3 Voltage:Low/Medium/High Voltage
Technical Parameters of our Power Cable
1). Standard: IEC60502; GB/T12706;IEC 60840;IEC62067;GB/T 11017;GB/Z 18890
2). Detailed description or construction:
    * Conductor: compacted or uncompacted copper or aluminium
    * Insulation: Cross-linked polyethylene (XLPE) or Polyvinyl chloride (PVC)
    * Filler: Polypropylene filament with lapped binding tape
    * Binder: Binding tape
    * Inner sheath: Polyvinyl chloride (PVC)
    * Armour: Galvanized steel wire armored (SWA) or steel tape armored (STA)
    *Sheath: Polyvinyl chloride (PVC)
3). The rated voltages U0/U(Um) of the cables considered in this standard are as follows:
U0/U(Um) =0.6/1(1.2)-3.6/6(7.2)-6/10(12)-6.35/11(12)-8.7/15(17.5)-12/20(24)-12.7/22(24)-18/30(36)-19/33(36)-26/35(40.5)KV
4). Voltage: 0.6/1kV, 1.8/3kV, 3.6/6kV, 6/10kV,6.35/11kV, 8.7/15kV, 12/20kV,12.7/22kV, 18/30kV,19/33kV,26/35kV
 In the voltage designation of cables U0/U(Um):
* U0 is the rated power frequency voltage between conductor and earth or metallic screen for which the cable is designed;
* U is the rated power frequency voltage between conductors for which the cable is designed;
* Um is the maximum value of the "highest system voltage" for which the equipment maybe used.
5). Application:
For laying indoors, in tunnel or cable trench with large difference of level able to bear external mechanical forces.
6). Marking: According to the customers' requirements
7). Nominal cross-sectional areas:
1.5mm2, 2.5mm2, 4mm2, 6mm2, 10mm2, 16mm2, 25mm2, 35mm2, 50mm2, 70mm2, 95mm2, 120mm2, 150mm2, 185mm2, 240mm2, 300mm2, 400mm2, 500mm2, 630mm2, 800mm2

Spec.& data
12/20kv

Conductor 
sections

Insulation 
Thickness(mm)

Inner 
sheathe thickness
(mm)

Steel Wire 
Dia.

Sheath 
thick
-

ness
(mm)

Cable 
Dia.
(mm)

Weight
(Kg/Km) Al

Conductor 
DC resistance

(Ώ/km)

Partial discharge
 test(
PC)

Testing 
voltage
(kV/5Min)

35

5.5

1.5

2.5

2.9

63.97

5719

≤0.8680 

≤20

30

50

5.5

1.6

2.5

3

66.75

6187

≤0.6410 

≤20

30

70

5.5

1.7

2.5

3.2

71.02

6882

≤0.4430 

≤20

30

95

5.5

1.7

2.5

3.3

74.25

7482

≤0.3200 

≤20

30

120

5.5

1.8

3.15

3.4

79.18

9068

≤0.2530 

≤20

30

150

5.5

1.9

3.15

3.5

82.5

9790

≤0.2060 

≤20

30

185

5.5

1.9

3.15

3.7

86.68

10667

≤0.1640 

≤20

30

240

5.5

2

3.15

3.8

92.27

11926

≤0.1250 

≤20

30

300

5.5

2.1

3.15

4

97.83

13247

≤0.1000 

≤20

30